Eaton 9PX 6000VA 5400W 208V Online Double-Conversion UPS – L6-30P or Hardwired Input, 2 L6-20R, 2 L6-30R, Lithium-ion Battery, Cybersecure Network Card, Extended Run, 3U Rack/Tower – 9PX6KL
Need Expert Advice?
Can’t find exactly what you’re looking for or need consultation? Chat directly with our Schneider/Eaton expert on WhatsApp!
Original price was: CAD $20,553.17.CAD $13,025.79Current price is: CAD $13,025.79.
Out of stock
SKU: 9PX6KL – Provides sine wave output, complete battery backup and power protection for mission-critical IT installations, edge networks and other advanced network applications.
- Keeps equipment running during outages to allow time for file saves and safe shutdown
- Improved lithium-ion batteries have lifespan up to 10 years – set it and forget it!
- Included NETWORK-M3 Gigabit network card enables full remote access and control
- Interactive LCD interface keeps you updated on critical load information in real time
- Optional extended battery modules allow expanded runtime to keep equipment powered
- 5-year limited warranty
Sustainable by Design
| UPC Code | 786689772598 |
|---|---|
| UPS Type | On-Line |
| Input Phase/th> | Single-Phase |
|---|---|
| Rated input current (Maximum Load) | 29A |
| Nominal Input Voltage(s) Supported | 200V AC; 208V AC; 220V AC; 230V AC; 240V AC |
| UPS Input Connection Type | Hardwire; L6-30P |
| Input Circuit Breakers | Recommended 30A upstream |
| UPS Input Cord Length (ft.) | 10 |
| UPS Input Cord Length (m) | 3.1 |
| Maximum Input Amps | 29 |
| Input Plug Type | NEMA L6-30P |
| Output Capacity (VA) | 6000 |
|---|---|
| Output Capacity (kVA) | 6 |
| Output Capacity (Watts) | 5400 |
| Output Capacity (kW) | 5.4 |
| Output Capacity Details | 5200VA / 4600W at 200V Output; 5400VA / 4800W at 208V Output; 5700VA / 5100W at 220V Output; 6000VA / 5300W at 230V Output; 6000VA / 5400W at 240V Output |
| Power Factor | 0.9 |
| Crest Factor | 3:1 |
| Nominal Voltage Details | 200V, 208V, 220V, 230V, 240V |
| Frequency Compatibility | 50 / 60 Hz |
| Output Circuit Breakers | 20A breaker protects L6-20R outlets |
| Output AC Waveform (Battery Mode) | Pure Sine wave |
| Output (Watts) | 5400 |
| Output AC Waveform (Battery Mode) | Pure Sine wave |
| Nominal Output Voltage(s) Supported | 200V; 208V; 220V; 230V; 240V |
| Output Receptacles | Hardwire; (2) L6-30R; (2) L6-20R |
| Battery Type | Lithium-ion (LiFePO4) |
|---|---|
| Runtime Full Load (min.) | 7.7 min. (5400W) |
| Runtime Half Load (min.) | 15.4 min. (2700W) |
| Expandable Runtime | Yes |
| Expandable Runtime Description | Add up to 4 extended battery modules (EBM). Part number 9PXEBM192RT-L |
| DC System Voltage (VDC) | 192 |
| Battery Access | Battery access door |
| Internal UPS Replacement Battery Cartridge | EBP-1801-L |
| Battery Replacement Description | Hot-swappable, replaceable batteries |
| Battery Management | Integrated battery management system (BMS) for temperature regulation and life cycle monitoring |
| Front Panel LCD Display | LCD graphical display |
|---|---|
| Switches | RPO / ROO |
| Alarm Cancel Operation | Press ESC to silence the alarm |
| Audible Alarm | Audible alarm indicates utility failure, low-battery, overload, other UPS/Battery fault or remote shutdown conditions |
| LED Indicators | 4 status-indicating LEDs |
| EMI / RFI AC Noise Suppression | Yes |
|---|---|
| AC Suppression Response Time | 0 ms |
| Primary Form Factor | Rackmount; Tower |
|---|---|
| Rack Height | 3U |
| Cooling Method | Fan |
| External Battery Pack Form Factor | Rack/Tower |
| Form Factors Supported | Rack/Tower |
| Installation Form Factors Supported with Included Accessories | 4 post 19 inch rackmount; Tower |
| Installation Form Factors Supported with Optional Accessories | 2 post rackmount ( RK2PC ) |
| Minimum Required Rack Depth (cm) | 76.20 |
| Unit Weight (kg) | 36.83 |
| Operating Temperature Range | 32° to 104°F (0° to 40°C) |
|---|---|
| Storage Temperature Range | 5° to 140°F (-15° to 60°C) |
| Relative Humidity | 0-95% non-condensing |
| AC Mode Efficiency Rating (100% Load) | 93 |
| AC Economy Mode Efficiency Rating (100% Load) | 98 |
| Online Mode Heat Dissipation (BTU/Hr) @ Full Load | 1233 |
| Battery Mode Heat Dissipation (BTU/Hr) @ Full Load | 1699 |
| Network Management Cards | INDGW-M2 ; RELAY-MS ; Network-M3 |
|---|---|
| Communications Interface | Pre-installed network card; RS-232; USB |
| High Availability UPS Features | Expandable battery backup; Hot swappable batteries; On-Line/Double-Conversion; Pure sine wave output; Remote management; Surge/noise protection; Zero transfer time |
|---|
| UPS Applications | Mission Critical Applications |
|---|
| Carton Notes | Pallet dims: 48in*40in*43in. (6/pallet) |
|---|
| Product Certifications | cUL Listed; NOM (Mexico); EN 62040-2; IEC 62040-2; ICC-ES AC156 OSHPD Seismic Certified |
|---|---|
| Product Compliance | CE (Europe); ENERGY STAR Qualified; FCC Part 15 Class A (USA); RoHS |
| Product Warranty Period (U.S. & Canada) | 5-year limited warranty |
|---|